Snifter mA+

Snifter for trend monitoring

Snifter mA+ brings whole new features to the Snifter series! With isolated 4...20 mA output this device is compatible with virtually all automation systems. Snifter mA+ can be used for monitoring filtration performance – on-line – continuously. Full compatibility with Sintrol Network and DustTool software with USB and RS485 communication ensures easy custom parameterization and allows for remote triggering of auto setup function.

EX models (IECEx and ATEX) available.
Wireless RF communication available.

Snifter mA+

Measurement Objects                 

Solid particles in a gas flow                           

Particle Size

0.3 µm or larger

Measurement Range

From 0.1 mg/m³

Measurement Principle 

Inductive Electrification

Protection Category

IP65

Sensor Length (total/measuring) 

250 mm / 185 mm  ı  9.8" / 7.3"

Power Supply

12 - 24 VDC

Power Consumption

3 W

Cable Connection

2 meter cable, 12 wires   ı   6.5 ft cable, 12 wires 

Process Connection

- NPT 1/2 " male thread

- NPT 1/2 " female thread welding socket (optional)

Output Signal

- Two output signals (100 - 280 mA)

- Isolated 4 - 20 mA output

Communication Interface

- Serial communication RS-485
- USB communication
- Wireless communication (optional)

Communication Protocol

- Modbus RTU, (RS-485)

- SNT network, (USB, Wireless, RS-485)

Alarm Settings

- Automatic
       - Alert: 5 x normal dust level
       - Alarm: 20 x normal dust level
- User selectable ranges

Signal Damping time

- Default at factory: 100 s
- Adjustable from 0 - 6000 s

Process Conditions

Temperature                              

Max 250 °C  ı  Max 482 °F                                   

Pressure

Max 200 kPa

Gas Velocity

Min 3 m/s  ı  Min 9.8 ft/s

Humidity

Max 95% RH (non-condensing)

Ambient Conditions

Temperature                              

- Starting -20 to +40°C  ı  -4 to 104 °F                     
- Running -40 to +60°C  ı  -40 to 140 °F

Humidity

Max 95 % RH (non-condensing)

Materials and Weight

Probe (wetted part) 

Stainless steel (AISI 316L)                            

Process Connection (wetted part)

Stainless steel (AISI 316L)

Enclosure

Aluminum

Probe Insulation (wetted part)

PEEK

Weight

0.7 kg  ı  1.5 lbs